D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0
Table 47:
D9133TTL-E Ethernet Status LED Function
LED
Description
1
Serial Port (Channel) 1
Status
2
Serial Port (Channel) 2
Status
3
Diagnostic
4
Network Link Status
* Non-fatal error
The network interface module (NIM) software version must be version 4.5 or above. To verify the
software version, initiate a Telnet session. Refer to
82
Troubleshooting
Function
NIM Software Version 4.5: On to indicate Serial Port (Channel) 1 is idle.
NIM software version 5.1b5 or 5.1b6: Off to indicate Serial Port (Channel) 1 is idle.
Not used.
Disregard status.
Glows steadily or flashes red in combination with the Channel 1 LED to indicate
diagnostics and error detection.
LED 3 solid red, LED 1 (Channel 1) flashing red:
1x
EPROM checksum error
2x
RAM error
3x
Network controller error
LED 3 flashing red, LED 1 (Channel 1) flashing red:
4x
Faulted network connection*
On to indicate the network port is connected to the network.
Using Telnet for Configuration
Bosch Security Systems, Inc. | 11/05 | F01U011024B
4x
EEPROM checksum error
5x
Duplicated IP address on the network*
6x
Software does not match hardware
5x
No DHCP response received
on page 86.
*