Bosch D9412GV2 Troubleshooting Manual page 77

Hide thumbs Also See for D9412GV2:
Table of Contents

Advertisement

.
A
B
C
1. Mark the wiring for all devices connected
to the SDI bus with the numbers of the
terminals.
2. Disconnect all devices from Terminal 29
through Terminal 32.
3. Set all DIP switches on a known good
keypad to ON (address number 1).
4. Directly wire the keypad to Terminal 29
through Terminal 32.
5. Using the D5200 Programmer or RPS,
go into GV2MAIN→Command
Centers →Command Center
Assignments.
6. At Command Center Assignment
Address "1", ensure that Scope is set to
"Panel Wide."
If using the D5200 Programmer,
disconnect it from the control panel and
release the reset pin.
Does the keypad operate correctly?
The SDI circuitry on the control panel
failed. Remove and replace the control
panel.
The SDI bus wiring has a short. Refer to
TTP46 Shorted Wiring
Use a digital voltmeter (DVM) and measure the input
power voltage on the NIM. Set the DVM to VDC.
Connect the red lead to the positive (+) terminal on
the NIM. Connect the black lead to the negative (
terminal. Refer to
Figure 33
DX4020, or in
Figure 34
D9133TTL-E.
Is the voltage +12 VDC to +13.8 VDC?
The power wiring between the control panel
and the NIM has an open condition. Refer to
TTP47 Open Wiring
Use a digital voltmeter (DVM) and measure the
voltage on the data circuit to the NIM. Connect the
red lead to Terminal G (green). Connect the black
lead to the negative (−) terminal. Refer to
on page
78
for the DX4020, or in
78
for the D9133TTL-E.
The voltage on these terminals is not a steady
voltage.
Is the lowest voltage indicated on the DVM less
than 3.5 VDC?
A
D
E
Bosch Security Systems, Inc. | 11/05 | F01U011024B
D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
on page 98.
)
on page
78
for the
on page
78
for the
on page 100.
Figure 33
Figure 34
on page
A
D
E
The network communication parameters for the
control panel are not correct. Use the RPS
software or the D5200 Programmer and
perform the programming procedure. Refer to
Using RPS (RAM IV)
D5200 Programmer
The data circuit between the control panel and the
NIM has an open condition. Refer to
Wiring
on page
100
.
Generate a signal by latching and unlatching the reset pin
on the control panel. Observe the serial transmit (SER-TX)
LED and the serial receive (SER-RX) LED on the NIM. Refer
to
Figure 37
and
Table 44
on page
Figure 38
and
Table 45
on page 82.
Do the SER-TX and SER-RX LEDs flash?
Generate another signal and observe the Xport LEDs
on the DX4020 or the Ethernet Status LEDs on the
D9133TTL-E. Refer to
DX4020 on page
80, or
the D9133TTL-E on pages
Do the LEDs flash or light?
Check the Ethernet network RJ-45 connection
and the Ethernet cable and connections.
Use a laptop PC and perform the procedure
described in
Using the PING Command
Does the ping command generate four replies?
Call Technical Support: (888) 886-6189.
Speak with a NetCom specialist.
Reconfigure the firewall. Refer to
Firewall in Windows XP Service Pack 2 for
Compatibility with RPS
Have the D6600 administrator call Technical Support: (888)
886-6189 and speak with a NetCom specialist.
on page
83
or
Using a
on page 84.
TTP47 Open
80
for the DX4020, or
Figure 39
and
Table 46
for the
Figure 40
and
Table 47
for
81
and 82.
on page 88.
Configuring the
on page
90
.
77