Bosch D9412GV2 Troubleshooting Manual page 73

Hide thumbs Also See for D9412GV2:
Table of Contents

Advertisement

.
Table 43 (continued): Phone Communication Sequence between Control Panel and Central Station
Step executed by the equipment
5.
The receiver answers and issues a
series of acknowledgement (ACK)
tones, one of which is specific to
the control panel.
6.
The control panel detects the
programmed ACK tone and sends
the event data.
7.
The receiver at the central station
issues a "kiss-off" signal.
8.
The control panel hangs up.
Bosch Security Systems, Inc. | 11/05 | F01U011024B
D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
Indicator of a successful step
Series of evenly spaced tones that
occur separately. These tones are
slow in comparison with the sounds
that occur when the control panel
sends data.
Steady high-pitched tone together
with rapidly changing connected or
separated tones. The connected
tones occur when data is sent using
modem format. The separated tones
occur when data is sent using BFSK
format.
Data transmission sounds stop.
Control panel does not attempt to
re-dial for the same event.
The equipment completes all steps
successfully, but the central station
has no recorded signals for the
assigned account number.
Modem format uses a four-digit account number. BFSK format uses a
three-digit account number. When programming a BFSK account
number using RPS, the first digit of the account number must be a 0.
When programming any account number using the D5200
Programmer, program the account number into digits 7 through 10.
For BFSK format, program digit 7 as 0, with the rest of the account
number in digits 8 through 10.
Action or Reference if the expected
indicator does not occur
Refer to
TTP36: The Receiver Does Not
Answer or Does Not Send ACK Tones
on page 75.
Refer to
TTP37: Control Panel Does Not
Send Event Data after ACK Tones
Occur, or Control Panel Attempts to
Communicate Again for the Same Event
on page 76.
Refer to
TTP37: Control Panel Does Not
Send Event Data after ACK Tones
Occur, or Control Panel Attempts to
Communicate Again for the Same Event
on page 76.
Refer to
TTP37: Control Panel Does Not
Send Event Data after ACK Tones
Occur, or Control Panel Attempts to
Communicate Again for the Same Event
on page 76.
Verify and record the communication
format and the account number.
1. Using RPS or your D5200
Programmer, select
GV2MAIN Panel Wide
Parameters Phone Parameters.
At the
prompt, record the
2.
Modem
entry. Yes indicates Modem
format, No indicates BFSK format.
Make sure that the correct format
is used for the receiver to which
the signals are sent.
3. Using RPS or your D5200
Programmer, select GV2MAIN Area
Wide Parameters Account Number
and record the account number for
each area. If an account number is not
correct, program the correct number
and verify the communications with
the central station.