Before mounting the Branch Gateway

1. Ensure that the rack is bolted to the floor and is earthquake-protected, if required.
2. If the Branch Gateway is being mounted in a rack with other equipment already
Result
Note:
The Branch Gateway weighs 21 pounds (9.5 kg) completely empty and up to 44 pounds (20
kg) when equipped with media modules, an S8300 Server, and two power supply units.
Note:

Mounting the Branch Gateway in the rack

The Branch Gateway is designed for single-person mounting. This assumes that the power
supplies were removed (see
1. Insert two mounting screws, one on either side of the rack.
2. Position the Branch Gateway in the rack so that the bottoms of the brackets are
3. Position the Branch Gateway in the rack.
4. Insert four rack mounting screws, two on each side.
5. Verify that the Branch Gateway is level and horizontal.
6. Tighten the rack mounting screws.
Quick Start for Hardware Installation: Avaya G450 Branch Gateway
If the rack is not securely fixed in place, do not proceed with the installation.
installed, the Branch Gateway must be positioned to avoid imbalance.
Removing power supply
These will be the bottom screws of the mounting brackets. Turn the screws only 3-4
times, so that a part of them is protruding.
resting on the protruding screws.
Ensure that there is adequate ventilation.
Avoid overtightening.
Mounting the Branch Gateway chassis
units).