Fireplace Placement Requirements

The fireplace requires a 4" clearance from the sides and 2" from the back of the fireplace to the
framing members. No material (insulation, framing, etc.) may be placed into this area.
Fireplace must be placed in a room with a minimum 96" ceiling.
Fireplace must be placed directly on the sub-floor or wood platform (not on linoleum or carpet).
Fireplace must be installed on a level surface capable of supporting the fireplace and vent.
This heater may be placed in a bedroom. Please be aware of the large amount of heat this
appliance produces when determining a location.

Clearances

When installed, walls in front of the fireplace must be a minimum 11" from the glass (5" from
the side stand-offs - see Figure 3).
Due to the high temperature, the heater should be located out of traffic and away from furniture
and draperies.
Fireplace must be placed so the vents below and above the glass do not become blocked.

Raised Fireplaces

The fireplace (and hearth, if desired) may be placed on a platform designed to support the
fireplace 250 Lbs.) and vent.
Minimum 60" Fireplace
Enclosure must also
meet 6" vent clearance.
(see "Hearth Requirements" for details)
© Travis Industries
Installation
Enclosure Height.
Optional Raised Hearth
(for qualified installers only)
4090807
Platform
Figure 6
100-01193_003