Programming Instructions For System Event Reporting - Interlogix xgen Installation & Programming Manual

Table of Contents

Advertisement

Example
Menu 3 – Zones
Zone 3 in Alarm
Partition Group
Zone sends alarm to Partition group
Menu 12 – Partition Groups
Partition Group 1
Partition 1
Partition 2
Event sent to lowest Partition
Menu 4 – Partitions
Partition 1
Channel Group
Partition sends event to
Channel Group
Menu 18 – Channel Groups
Channel Group 1
Channel 1
Channel 2
Channel 3
Next
Program Users
Program advanced Schedules and Alternate Zone Profiles

Programming Instructions for System Event Reporting

Pre-conditions
Communicator must be programmed (see Communicator Programming).
Event Lists must be programmed (see Event Programming).
Channels and Channel Groups must be programmed (see Channel
Programming).
Notes
The system event will only be reported by a channel, if that Channel
includes that event in the associated Event List(s).
Take note of the Sequence Attempts under Communicator – System
Event Reporting (6.11.2). This is the number of times xGen will attempt
the sequence of Channels you set up in this section.
xGen Installation & Programming Guide
Menu 5 – Channels
Channel checks to see if the
event is on its Event List, if yes it
will attempt to send, if not then it
stops
Channel Group sends Event
to every Channel it contains
Channel 1
Control Room 1
Event List = 1
Channel Attempts = 3
Next Channel = 4
Channel 2
Control Room 2
Event List = 1
Next Channel = 5
Channel 3
Email
Event List = 2
Next Channel = 0
Channel 4
Control Room 1
Event List = 1
Channel Attempts = 3
Next Channel = 0
If it does not succeed after
Channel Attempts, it will try
sending on the next Channel
Channel 5
Control Room 2
Event List = 1
Next Channel = 0
107