Lock Out - REMEHA HMI Gas 610 ECO PRO Installation, User And Service Manual

Hide thumbs Also See for HMI Gas 610 ECO PRO:
Table of Contents

Advertisement

HMI Gas 310/610 ECO PRO
Shutdown
Description
code
No flame during operation
5v[22
Gas leakage control fault
5v[24
Internal error on the SU PCB
5v[25
(1) These lock-outs are not stored in the fault memory
Error
Description
code
Storage unit PSU
e[00
parameter not found
The safety parameters
e[01
are incorrect
Flow temperature sensor
e[02
short circuited
Flow temperature sensor
e[03
open circuit
051112 - 125482-03
Probable causes
No ionization current
4
Bad connection
4
Gas valve unit defective
4
Gas leakage control VPS
4
faulty
6.1.3.
If the blocking conditions still exist after several start up attempts, the
boiler will switch into locking mode (fault). The display shows :
In a red flashing display:
4 The symbol c
4 The symbol J
4 The fault code (for example e[01)
4 Press the J key for 2 seconds. If the error code continues to
display, search for the cause in the error table and apply the
solution.
The error code is important for rapid and correct tracking
of the type of problem and for any technical assistance from
Remeha.
Probable causes
Bad connection
4
Bad connection
4
PSU defective
4
Bad connection
4
Sensor not or badly
4
connected
Sensor fault
4
Bad connection
4
Sensor not or badly
4
connected
Sensor fault
4
Checking / solution
Purge the gas supply to remove air
4
Check that the gas valve is fully opened
4
Check the supply pressure
4
Check the operation and setting of the gas
4
valve unit
Check that the air inlet and flue gas
4
discharge flues are not blocked
Check that there is no recirculation of flue
4
gases
Check the wiring
4
Replace the gas valve unit
4
Replace gas leakage control VPS
4
Replace the SU PCB
4

Lock out

Checking / solution
Check the wiring
4
Check the wiring
4
Replace PSU
4
Check the wiring
4
Check that the sensors are operating correctly
4
Check that the sensor has been correctly fitted
4
Replace the sensor if necessary
4
Check the wiring
4
Check that the sensors are operating correctly
4
Check that the sensor has been correctly fitted
4
Replace the sensor if necessary
4
6. Troubleshooting