8. If necessary, set other parameters by selecting them using the
[-] or [+] keys.
9. Press the > key 2 times to return to the current operating
mode.
The boiler also returns to operating status if no keys are
pressed for 3 minutes.
5.3.4.
Setting the maximum heat input for central
heating operation
Type Gas 310- ECO PRO 575
Maximum heat input (natural gas)
M
Factory setting
F
Power input (kW)
Q
Fan rotation speed (rpm)
R
The speed can be changed using parameter p17. A linear
relationship exists between the speed and the input: See graph. A
graph for the other boilers can be produced in the same way.
1. Press the two keys f simultaneously and then key [+] until the
symbol ? flashes on the menu bar.
2. Select the installers menu using the key S . c0de appears
on the display.
3. Use keys [-] or [+] to input the installer code 0012 .
4. Confirm using key S . p[1 is displayed with 1 flashing.
5. Press the [+] key to go to parameter p[17 .
6. Confirm using key S .
7. Press the [+] button to reduce the speed from 54 to 50 , for
example.
8. Confirm the value with the S key.
9. Press the > key 2 times to return to the current operating
mode.