HMI Gas 310/610 ECO PRO
3x
...x
3x
...x
051112 - 125482-03
5.3.5.
1. Press the two keys f simultaneously and then key [+] until the
2. Select the installers menu using the key S . c0de appears
3. Use keys [-] or [+] to input the installer code 0012 .
4. Confirm using key S . p[1 is displayed with 1 flashing.
5. Press the [+] key several times. p[df is displayed with df
6. Press the S key. df[x is displayed with x flashing. This is
7. Enter the value of X shown on the type plate using the [-] or [+]
8. Confirm the value with the S key, df[y is displayed with y
9. Enter the value of Y shown on the type plate using the [-] or [+]
10.Confirm the value with the S key. The factory settings are reset.
11.The display returns to the current operating mode.
T000820-H
5.3.6.
After removing a control PCB, an auto-detect must be carried out. To
do this, proceed as follows:
1. Press the two keys f simultaneously and then key [+] until the
2. Select the installers menu using the key S . c0de appears
3. Use keys [-] or [+] to input the installer code 0012 .
4. Confirm using key S . p[1 is displayed with 1 flashing.
5. Press the [+] key several times. p[Zd is displayed with Zd
6. Confirm using key S . Auto-detect is carried out.
7. The display returns to the current operating mode.
T000445-B
Return to the factory settings
CAUTION
By restoring the factory settings, customized settings can
also be erased. So first write down all the customized
parameters (eg settings for attached accessories such as
a flue gas valve or gas leak control). Adjust these specific
settings again after the factory settings have been
restored.
symbol ? flashes on the menu bar.
on the display.
flashing.
the current value of X for dF. Check this against the value of X on
the type plate.
key.
flashing. This is the current value of Y for dU. Check this against
the value of Y on the type plate.
key.
Carrying out an auto-detect
symbol ? flashes on the menu bar.
on the display.
flashing.
5. Commissioning