5. Commissioning
State 5t
3 Burner for central heating operation
5 Burner stop
6 Boiler stop (End of heat demand)
8 Control stop
9 Blocking
5.3
Changing the settings
Parameter
Description
Supply temperature: T
p1
Post-circulation of the pump
p2
Boiler regulation
p3
13
Sub-status 5v
30 Temperature control
31 Limited temperature control (ΔT safety)
32 Output control
33 Increase protection level 1 (Modulate down)
34 Increase protection level 2 (Part load)
35 Increase protection level 3 (Blockage)
36 Modulate up for flame control
37 Temperature stabilisation time
38 Cold start
40 Burner off
41 Post ventilation
42 Fan OFF
43 Close flue gas damper (Accessory)
44 Stop fan
45 Close external gas valve
60 Pump post circulation
61 Pump off
62 Close hydraulic valve
63 Start anti-hunting
0 Wait for burner start
1 Anti-hunting
xx Shutdown code xx
The boiler control panel is set for the most common heating
systems. With these settings, practically all heating systems operate
correctly. The user or installer can optimise the parameters according
to own preferences.
For the settings of the Gas 610 ECO PRO boiler:
The parameters and settings described are for each boiler
module. Each parameter changing must therefore be done
identical on each module.
5.3.1.
n Boiler type Gas 310 ECO PRO
Adjustment range
20 to 90 °C
SET
1 to 98 minutes
99 minutes = continuous
0 = Heating deactivated
1 = Heating activated
Parameter descriptions
HMI Gas 310/610 ECO PRO
Factory setting
Gas 310 ECO PRO
285 355 430 500 575 650
80
5
1