Readout From The Hour Counter And Percentage Of Successful Starts; Status And Sub-Status - REMEHA HMI Gas 610 ECO PRO Installation, User And Service Manual

Hide thumbs Also See for HMI Gas 610 ECO PRO:
Table of Contents

Advertisement

HMI Gas 310/610 ECO PRO
5x
2x
State 5t
0 Rest
1 Boiler start (Heat demand)
2 Burner start
051112 - 125482-03
5.2.2.
1. Press the two keys f simultaneously and then key [+] until the
symbol \ flashes on the menu bar.
2. Press the S key. hr and the number of hours of boiler
operation 3600 (for example) are displayed alternately.
3. Press the [+] key. The display shows D . hr is displayed,
alternating with the number of operating hours in central heating
operation 560 (for example).
4. Press the [+] key. The display shows @ . 5Z is displayed,
alternating with the percentage of successful starts 92 % (for
example).
5. Press the > key 2 times to return to the current operating
mode.
T000816-G
5.2.3.
The information menu Q gives the following status and sub-status
numbers:
Sub-status 5v
0 Rest
1 Anti-hunting
2 Open hydraulic valve
3 Start pump
4 Wait for the correct temperatures for burner start
10 Open external gas valve
11 Fan ON
12 Open flue gas damper (Accessory)
13 Pre-ventilation
14 Wait for release signal
15 Burner on
16 Gas valve leak proving system VPS
17 Pre-ignition
18 Main ignition
19 Flame detection
"0 Intermediate ventilation
Readout from the hour counter and
percentage of successful starts

Status and sub-status

5. Commissioning
12