5. Commissioning
Parameter
Description
Minimum gas pressure
check Gps
p29
(Accessory)
Hydraulic valve running
time HdV
p30
(If connected)
Flue gas damper running
time FgV
p31
If connected (Accessory)
Release waiting time
p32
Gas valve leak proving
system VPS
p33
(Accessory)
Mains detection phase
p34
Shutdown input function
p35
From Analogue output (0 -
10V)
p36
SCU-S05 control PCB
From Analogue input
(0-10V)
p37
SCU-S05 control PCB
Average flow temperature
p38
factor
Display units
p39
Maintenance message
p40
Service operating hours
p41
Service burning hours
p42
Setting the pump speed
(Minimum pump speed for
p43
central heating operation)
Setting the pump speed
(Maximum pump speed for
p44
central heating operation)
ΔT Modulate down
p45
Detection of connected
Zd
SCUs
df and dV Factory setting
17
Adjustment range
0 = Not connected
1 = Connected
0 to 255 seconds
0 to 255 seconds
0 to 255 seconds
0 = Not connected
1 = Connected
0 = Off
1 = On
1 = Shutdown without frost-protection
2 = Shutdown with frost protection
3 = Lock-out with frost protection (Pump
only)
0 =0-10 V Wilo control PCB
1 = 0-10 V Grundfos control PCB
2 = PWM pump
3 = Heat output feedback
4 = Temperature feedback
0 =OpenTherm regulator
1 = Analogue temperature-based control
(°C)
2 = Analogue heat output-based control (%)
Do not modify
0 = °C / bar
1 = F / PSI
0 = Service messages off
1 = Service messages on
2 = Customized service message
( x 100)
Do not modify
( x 100)
Do not modify
2 - 10 (x 10%)
6 - 10 (x 10%)
10 to 30 °C
0 = No detection
1 = Detection
To restore the factory settings or when
replacing the main PCB, enter the values
dF and dU from the type plate in parameters
df and dV
HMI Gas 310/610 ECO PRO
Factory setting
Gas 610 ECO PRO
570 710 860 1000 1150 1300
0
0
0
0
0
1
1
0
1
6
0
0
175
30
2
10
25
0
X
Y
051112 - 125482-03