HMI Gas 310/610 ECO PRO
Parameter
Description
Display screen
p4
Brightness of display lighting
p5
Maximum fan speed
p17
Minimum fan speed
p18
offset Minimum fan speed
p19
Start speed
p20
Maximum flow temperature
p21
of system
Heat curve set point
(Maximum outside
temperature)
p22
Only with an outside
temperature sensor
(Accessory)
Heat curve set point
(Supply temperature)
Only with an outside
p23
temperature sensor
(Accessory)
Heat curve set point
(Minimum outside
temperature)
p24
Only with an outside
temperature sensor
(Accessory)
Antifreeze temperature
Only with an outside
p25
temperature sensor
(Accessory)
Fault relay function X4
p26
(If connected)
Fault relay function X5
p27
(If connected)
Minimum water pressure
Wps
Only with the hydraulic
p28
pressure sensor connected
(Accessory)
Minimum gas pressure
check Gps
p29
(Accessory)
Hydraulic valve running time
HdV
p30
(If connected)
Flue gas damper running
time FgV
p31
If connected (Accessory)
051112 - 125482-03
Adjustment range
0 = Simple
1 = Comprehensive
2 = Automatic switching to simple after 3
minutes
3 = Automatic switching to simple after 3
minutes; Key blocking is active
0 = Dimmed
1 = Bright
G20 (Gas H)
(x100 rpm)
G20 (Gas H)
(x100 rpm)
Do not modify
(x1 rpm)
Do not modify
(x100 rpm)
0 to 90 °C
0 to 30 °C
0 to 90 °C
-30 to 0 °C
from - 30 to 0°C
0 = Operation signal
1 = Alarm signal
0 = Operation signal
1 = Alarm signal
0 - 7 bar (x 0.1 bar)
0 = Not connected
0 = Not connected
1 = Connected
0 to 255 seconds
0 to 255 seconds
5. Commissioning
Factory setting
Gas 310 ECO PRO
285 355 430 500 575 650
2
1
52
55
35
38
43
14
15
9
10
11
0
50
50
50
0
25
25
13
14
14
90
20
20
-15
- 10
0
1
0
0
0
0
41
10
50
14
14