5. Commissioning
Parameter
Description
Release waiting time
p32
Gas valve leak proving
system VPS
p33
(Accessory)
Mains detection phase
p34
Shutdown input function
p35
From Analogue output (0 -
10V)
p36
SCU-S05 control PCB
From Analogue input (0-10V)
p37
SCU-S05 control PCB
Average flow temperature
p38
factor
Display units
p39
Maintenance message
p40
Service operating hours
p41
Service burning hours
p42
Setting the pump speed
(Minimum pump speed for
p43
central heating operation)
Setting the pump speed
(Maximum pump speed for
p44
central heating operation)
ΔT Modulate down
p45
Detection of connected SCUs
Zd
df and dV Factory setting
15
Adjustment range
0 to 255 seconds
0 = Not connected
1 = Connected
0 = Off
1 = On
1 = Shutdown without frost-protection
2 = Shutdown with frost protection
3 = Lock-out with frost protection (Pump only)
0 =0-10 V Wilo control PCB
1 = 0-10 V Grundfos control PCB
2 = PWM pump
3 = Heat output feedback
4 = Temperature feedback
0 =OpenTherm regulator
1 = Analogue temperature-based control (°C)
2 = Analogue heat output-based control (%)
Do not modify
0 = °C / bar
1 = F / PSI
0 = Service messages off
1 = Service messages on
2 = Customized service message
( x 100)
Do not modify
( x 100)
Do not modify
2 - 10 (x 10%)
6 - 10 (x 10%)
10 to 30 °C
0 = No detection
1 = Detection
To restore the factory settings or when
replacing the main PCB, enter the values dF
and dU from the type plate in parameters
df and dV
HMI Gas 310/610 ECO PRO
Factory setting
Gas 310 ECO PRO
285 355 430 500 575 650
0
0
1
1
0
1
6
0
0
175
30
2
10
25
0
X
Y
051112 - 125482-03