Fireplace Insert Installation
Insert Placement Requirements
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" (915mm) of the front of the insert (Figure 3 "q").
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements in Figure 3 must be met. Follow the
clearances for the type of fireplace being used – (masonry or zero-clearance-metal).
Side
k
Wall
l
p
q
Hearth Requirements
Must extend 16" (USA) or 18" (Canada) in front of the insert and 8" on both sides.
Must be non-combustible and at least .018" thick (26 gauge)
Masonry Fireplace Requirements
Chimney must have a clay tile liner or a stainless steel liner (positive connection).
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired
prior to installation of the insert.
Chimney height: 15' (4.5M) minimum; 33' (10M) maximum (measured from base of insert).
Entire fireplace, including chimney, must meet local building requirements.
The fireplace insert must be placed on a masonry hearth built to UBC standards.
© Travis Industries
n
m
x
o
(for qualified installers only)
Minimum
Clearances
k Sidewall
l Side Facing
(non-
combustible)
m Top Facing
(non-
combustible)
n Mantel
(combustible)
o Front Hearth
(does not
include insert
extension "x")
p Side Hearth
q Front of Insert
x Extension Onto
Hearth
100-01259
Masonry
Z.C. (Metal)
Fireplace
Fireplace
9"
9"
229mm
229mm
9"
9"
229mm
229mm
39"
39"
991mm
991mm
41.5"
41.5"
1055mm
1055mm
16"
16"
407mm (US)
407mm (US)
- - - - - - - - - - -
- - - - - - - - - - -
18"
18"
458mm
458mm
(Canada)
(Canada)
8"
8"
204mm
204mm
36"
36"
915mm
915mm
0"
0"
0mm
0mm
Figure 3