Fireplace Insert Installation
Insert Placement Requirements
•
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" (915mm) of the front of the insert (item "q" below).
•
Insert and hearth must be installed on a level, secure floor
•
The minimum clearances, facing, and hearth requirements listed below must be met.
Minimum Clearances
k Sidewall
l Side Facing (non-combustible)
m Top Facing (non-combustible)
n Mantel (combustible – maximum 12" 305mm deep)
o Front Hearth
p Side Hearth
q Front of Insert
s Mantel Column (max. 8" 204mm deep)
x Extension Onto Hearth
© Travis Industries
Side
k
Wall
s
l
p
q
100-01342
(for qualified installers only)
11.625" 296mm
6.25" 159mm
37.5" 953mm
37.5" 953mm
16" 407mm
(USA)
18" 458mm
(Canada)
8" 204mm
36" 915mm
6.25" 159mm
1.5" 39mm
n
m
x
o
9
4131101