[ II Restrictions ]

(2) High COP combinations

Outdoor units
EP200
YJM-A
EP250
YJM-A
EP300
YJM-A
EP400
YSJM-A
EP450
YSJM-A
EP500
YSJM-A
YSJM-A1
EP550
YSJM-A
EP600
YSJM-A
EP650
YSJM-A
EP700
YSJM-A
YSJM-A1
EP750
YSJM-A
YSJM-A1
EP800
YSJM-A
YSJM-A1
EP850
YSJM-A
EP900
YSJM-A
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE10040
Composing units
-
-
-
-
-
-
-
-
-
EP200
EP200
-
EP250
EP200
-
EP300
EP200
-
EP250
EP250
-
EP300
EP250
-
EP300
EP300
-
EP250
EP200
EP200
EP300
EP200
EP200
EP250
EP250
EP200
EP300
EP250
EP200
EP250
EP250
EP250
EP300
EP300
EP200
EP300
EP250
EP250
EP300
EP300
EP250
EP300
EP300
EP300
Maximum total ca-
Maximum num-
pacity of connect-
ber of connect-
able indoor units
able indoor units
100
-
260
125
-
325
150
-
390
200
-
520
225
-
585
250
-
650
275
-
715
300
-
780
325
-
845
350
-
910
375
-
975
400
-
1040
425
-
1105
450
-
1170
- 18 -
Types of connectable
indoor units
17
P15 - P200 models
R410A series indoor units
21
26
34
P15 - P500 models
R410A series indoor units
39
43
47
50
GB