[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10040
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
Unit
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ ft ]
Total pipe length
[ lbs-oz ]
Pulse
MPa
[ psi ]
Discharge (TH4)
Heat exchanger inlet
(TH3)
Accumulator inlet
Accumulator outlet
°C [ °F ]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
inlet
PUHY-P400YJM-A
-
100/100/100/100/100/100/100/100/50
-
kg
A
V
Hz
102
332/332/332/332/332/332/332/332/373
1920
2.91/ 0.60
[422/ 87]
89 [192]
-2 [28]
-4 [25]
-4 [25]
-4 [25]
40 [104]
- 151 -
Outdoor unit model
PUHY-P850YSJM-A
PUHY-P450YJM-A
20°C/- [68°F/- ]
7°C/ 6°C
[45°F/ 43°F]
9
9
5 [17]
10 [33]
95 [312]
Hi
37.5 [83]
45.5
400
117
0
1920
2.91/ 0.60
[422/ 87]
89 [192]
-2 [28]
-4 [25]
-4 [25]
-4 [25]
40 [104]
39 [102]
87 [189]
GB