[ II Restrictions ]

[6] An Example of a System to which an ME Remote Controller is connected

(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
ON
OS2
53
TB3
M1 M2
TB7
M1 M2
S
To be left
unconnected
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
ON
OS2
56
TB3
M1 M2
TB7
M1 M2
S
To be left
unconnected
(2) Cautions
1) ME remote controller and MA remote controller cannot
both be connected to the same group of indoor units.
2) No more than 3 ME remote controllers can be connected
to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
4) Replace the power jumper connector of the control board
from CN41 to CN40 on only one of the outdoor units.
(not required if power to the transmission line for central-
ized control is supplied from a controller with a power-
supply function, such as GB-50ADA)
5) Provide an electrical path to ground for the S terminal on
the terminal block for centralized control on only one of
the outdoor units.
6) A transmission booster must be connected to a system
in which the total number of connected indoor units ex-
ceeds 20.
7) A transmission booster is required in a system to which
more than 16 indoor including one or more indoor units
of the 200 model or above are connected.
8) When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
HWE10040
L11
Move the male connector
Leave the male
from CN41 to CN40.
connector on
SW2-1 OFF ON
CN41 as it is.
SW2-1 OFF
ON
OS1
OC
52
51
TB3
TB3
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
To be left
unconnected
To be connected
L21
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW2-1 OFF
ON
SW2-1 OFF
ON
OS1
OC
55
54
TB3
TB3
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
To be left
unconnected
To be left
unconnected
System controller
A B S
L12
Group
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1 M2
M1 M2
S
1 2
S
1 2
A B
A B
101
102
RC
RC
L22
Group
IC
IC
04
05
TB5
TB5
TB15
TB15
M1 M2
M1 M2
S
1 2
S
1 2
A B
A B
154
104
RC
RC
Note1 When only the LM adapter is connected,
leave SW2-1 to OFF (as it is).
Note1
Note2 LM adapters require the power supply
capacity of single-phase AC 208/230V.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
Same as [5] 4.
3) ME remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
m1 10m [32ft]
m2+m3 10m [32ft]
If the standard-supplied cable must be extended, use a
cable with a diameter of 1.25mm
of the cable that exceeds 10m [32ft] must be included in
the maximum indoor-outdoor transmission line distance
described in (1).
When connected to the terminal block on the Simple re-
mote controller, use cables that meet the following cable
size specifications: 0.75 - 1.25 mm
4) Maximum line distance via outdoor unit
2
(1.25mm
or larger)
Same as [5] 4.
- 38 -
Interlock operation with
the ventilation unit
Group
LC
IC
03
07
TB5
TB15
TB5
M1 M2
M1 M2
S
1 2
S
A B
103
RC
Group
LC
IC
06
08
TB5
TB5
TB15
M1 M2
M1 M2
S
1 2
S
A B
106
RC
2
[AWG22 to 16])
2
[AWG16]. The section
2
[AWG18-14].