Remote Controller Function Selection Via The Me Remote Controller; To Delete Group Settings; To Delete Interlock Settings - Mitsubishi Electric PUHY-P200 Service Handbook

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[ IV Remote Controller ]
(A) To delete group settings
<Successful completion of deletion>
will be displayed in the room temperature display window.
- If a transmission error occurs, the selected setting will not be
deleted, and the display will appear as shown below.
In this case, repeat the steps above.
<Deletion error>
will be displayed in the room temperature display window.
To go back to the normal display, follow step
(4) Making (A) Group settings and (B) Interlock settings of a group from any arbitrary remote controller
(A) Group settings and (B) Interlock settings of a group can be made from any arbitrary remote controller.
Refer to (B) Interlock Settings under section 1 Group Settings/Interlock Settings for operation procedures.
Set the address as shown below.
(A) To make group settings
Interlocked unit address display window...Remote controller address
Indoor unit address display window...........The address of the indoor unit to be controlled with the remote controller
(B) To make interlock settings
Interlocked unit address display window...LOSSNAY address
Indoor unit address display window..........The address of the indoor unit to be interlocked with the LOSSNAY

2. Remote controller function selection via the ME remote controller

In the remote controller function selection mode, the settings for four types of functions can be made or changed as necessary.
1) Skip-Auto-Mode setting
The automatic operation mode that is supported by some simultaneous cooling/heating type units can be made unselectable via the ME remote
controller.
2) Operation mode display selection mode (Display or non-display of COOL/HEAT during automatic operation mode)
When the automatic operation mode is selected, the indoor unit will automatically perform a cooling or heating operation based on the room
temperature. In this case,
This setting can be changed so that only
3) Room temperature display selection mode (Display or non-display of room temperature)
Although the suction temperature is normally displayed on the remote controller, the setting can be changed so that it will not appear on the
remote controller.
4) Narrowed preset temperature range mode
The default temperature ranges are 19 C to 30 C in the cooling/dry mode and 17 C to 28 C in the heating mode and 19 C to 28 C in the auto mode.
By changing these ranges (raising the lower limit for the cooling/dry mode and lowering the upper limit for the heating mode), energy can be saved.
NOTE
When making the temperature range setting on the simultaneous cooling/heating type units that supports the automatic operation mode to save on
energy consumption, enable the Skip-Auto-Mode setting to make the automatic operation mode unselectable. If the automatic operation mode is
selected, the energy-saving function may not work properly.
When connected to the air conditioning units that do not support the automatic operation mode, the setting for the Skip-Auto-Mode, restricted preset
temperature range mode (AUTO), and operation mode display selection mode are invalid. If an attempt is made to change the preset temperature range,
"LIMIT TEMP." appears on the display.
TEMP.
ON/OFF
CLOCK→ON→OFF
TIMER SET
PAR-F27MEA
HWE10040
or
will appear on the remote controller display.
will appear on the display.
Normal display
1
1
Remote controller function selection mode
Skip-Auto-Mode setting
2
*2
Temperature range setting mode (AUTO)
2
Operation mode display selection mode (Display or non-display of the automatic mode)
5
FILTER
2
CHECK TEST
Restricted preset temperature range mode (Cooling)
4
2
Restricted preset temperature range mode (Heating)
2
Room temperature display selection mode
(B) To delete interlock settings
(Displayed alternately)
.
10
[Function selection mode sequence on the remote controller]
3
3
2
*1
*1
3
3
*2
3
3
- 64 -
If deletion is successfully
completed,
the unit type display window.
If the deletion fails,
appear in the unit type display
window. In this case, repeat the
steps above.
[Normal display]
1
: Press and hold the [CHECK] and
[
] buttons simultaneously
for two seconds.
2
: [SET TEMP. (
) ] button
3
: [SET TEMP. (
) ] button
2
3
*1 : Skip-Auto-Mode is enabled
*2 : Skip-Auto-Mode is disabled
- -
will appear in
will
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents