Mitsubishi Electric PUHY-P200 Service Handbook page 100

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[ VII Control ]
(2) ME remote controller (PAR-F27MEA)
Set the address of the remote controller with the rotary switch.
Main remote controller
Sub remote controller
Setting of rotary switch
*1
01-99
00
*1. At factory shipment, the rotary switch is set to 01.
*2. The address range that can be set with the ME remote controller is between 101 and 200. When the dials are set to
a number between 01 and 99, the 100's digit is automatically set to [1]. When the dials are set to 00, the 100's digit is
automatically set to [2].
To set addresses, use a precision slotted screw driver [2.0 mm [0.08 in] (w)], and do not apply than 19.6N.
The use of any other tool or applying too much load may damage the switch.
HWE10040
0
0
Remote controller unit
Example: In case of address 108
Address setting range
101-150
151-200
101-199 with the 100's digit automatically being set to 1
- 91 -
Rotary switch
0
0
10's digit 1's digit
(left)
(right)
Setting method
Add 100 to the smallest address of all the indoor units in the
same group.
Add 150 to the smallest address of all the indoor units in the
same group.
Address No.
200
*2
GB