Refrigerant Pipe Size - Mitsubishi Electric PUHY-P200 Service Handbook

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[ II Restrictions ]

1. Refrigerant pipe size

(1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdoor unit pipe size)
Outdoor unit set name
(total capacity)
200 model
250 model
300 model
350 model
400 model
450 model
500 model
550 model
600 model
650 model
700 - 800 model
850 - 1250 model
*1. Use ø12.7 [1/2"] pipes if the piping length exceeds 90 m [295 ft].
*2. Use ø12.7 [1/2"] pipes if the piping length exceeds 40 m [131 ft].
(2) Size of the refrigerant pipe between the first branch and the indoor unit (indoor unit pipe size)
model
20 - 50 models
63 - 140 models
200 model
250 model
400 model
500 model
(3) Size of the refrigerant pipe between the branches for connection to indoor units
Total capacity of the
downstream units
- 140
P141 - P200
P201 - P300
P301 - P400
P401 - P650
P651 - P800
P801 -
HWE10040
Liquid pipe size (mm) [inch]
ø9.52 [3/8"]
*1
ø9.52 [3/8"]
*2
ø9.52 [3/8"]
ø12.7 [1/2"]
ø12.7 [1/2"]
ø15.88 [5/8"]
ø15.88 [5/8"]
ø15.88 [5/8"]
ø15.88 [5/8"]
ø15.88 [5/8"]
ø19.05 [3/4"]
ø19.05 [3/4"]
Pipe diameter (mm) [inch]
Liquid pipe
ø6.35 [1/4"]
Gas pipe
ø12.7 [1/2"]
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø15.88 [5/8"]
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø19.05 [3/4"]
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø22.2 [7/8"]
Liquid pipe
ø12.7 [1/2"]
Gas pipe
ø28.58 [1-1/8"]
Liquid pipe
ø15.88 [5/8"]
Gas pipe
ø28.58 [1-1/8"]
Liquid pipe size (mm) [inch]
ø9.52 [3/8"]
ø9.52 [3/8"]
ø9.52 [3/8"]
ø12.7 [1/2"]
ø15.88 [5/8"]
ø19.05 [3/4"]
ø19.05 [3/4"]
Gas pipe size (mm) [inch]
ø19.05 [3/4"]
ø22.2 [7/8"]
ø22.2 [7/8"]
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
ø34.93 [1-3/8"]
ø41.28 [1-5/8"]
Gas pipe size (mm) [inch]
ø15.88 [5/8"]
ø19.05 [3/4"]
ø22.2 [7/8"]
ø28.58 [1-1/8"]
ø28.58 [1-1/8"]
ø34.93 [1-3/8"]
ø41.28 [1-5/8"]
- 44 -
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents