Mitsubishi Electric PUHY-P200 Service Handbook page 172

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
SC (LEV1)
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10040
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
Unit
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ ft ]
Total pipe length
kg
[ lbs-oz ]
Hz
Pulse
MPa
[ psi ]
Discharge (TH4)
Heat exchanger inlet
(TH3)
Accumulator inlet
Accumulator outlet
°C [ °F ]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
inlet
PUHY-
P350YJM-A
100/100/100/100/100/100
-
-
A
V
101
332/332/332/332/332/332
1440
2.91/ 0.60
[422/ 87]
89 [192]
-2 [28]
-4 [25]
-4 [25]
-4 [25]
40 [104]
- 163 -
Outdoor unit model
PUHY-P1100YSJM-A
PUHY-
P350YJM-A
20°C/- [68°F/- ]
7°C/ 6°C
[45°F/ 43°F]
11
11
100/100/100/100/100
5 [17]
10 [33]
115 [378]
Hi
52.2 [115]
57.8
400
101
332/332/332/332/332
0
1440
2.91/ 0.60
[422/ 87]
89 [192]
-2 [28]
-4 [25]
-4 [25]
-4 [25]
40 [104]
39 [102]
87 [189]
PUHY-
P400YJM-A
102
1575
2.91/ 0.60
[422/ 87]
89 [192]
-2 [28]
-4 [25]
-4 [25]
-4 [25]
40 [104]
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents