Mitsubishi Electric PUHY-P200 Service Handbook page 259

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[ IX Troubleshooting ]
7100
1. Error Code
7100
Total capacity error
2. Error definition and error detection method
The model total of indoor units in the system with one outdoor unit exceeds limitations.
3. Error source, cause, check method and remedy,
Error source
Outdoor unit
(1)
(2)
(3)
HWE10040
Cause
The model total of indoor units in the sys-
tem with one outdoor unit exceeds the fol-
lowing table.
Model
Qj Total
200 model
53
69
250 model
300 model
86
350 model
96
400 model
108
450 model
121
500 model
138
550 model
155
172
600 model
650 model
177
700 model
190
750 model
207
800 model
224
850 model
241
900 model
258
254
950 model
1000 model
270
1050 model
284
1100 model
296
1150 model
312
1200 model
324
1250 model
338
The model selection switches (SW5-1 - 5-
4) on the outdoor unit are set incorrectly.
SW5
Model
1
2
200 model
OFF
ON
OFF
250 model
ON
ON
OFF
300 model
OFF
OFF
ON
350 model
OFF
ON
ON
400 model
ON
ON
ON
450 model
OFF
OFF
OFF
The outdoor unit and the auxiliary unit
(OS) that is connected to the same system
are not properly connected.
1)
Check the Qj total (capacity code total) of indoor
units connected.
2)
Check the Qj setting (capacity code) of the con-
nected indoor unit set by the switch (SW2 on in-
door unit board).
When the model name set by the switch is differ-
ent from that of the unit connected, turn off the
power source of the outdoor and the indoor units,
and change the setting of the Qj (capacity code).
3)
Indoor unit Qj table
Check the setting for the model selection switch
on the outdoor unit (Dipswitches SW5-1 - 5-4 on
the outdoor unit control board).
3
4
OFF
OFF
OFF
OFF
OFF
ON
Confirm that the TB3 on the OC and OS are
properly connected.
- 250 -
Check method and remedy
Model
Qj
15
3
20
4
25
5
32
6
40
8
50
10
63
13
71
14
80
16
100
20
125
25
140
28
200
40
250
50
GB

Hide quick links: