[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10040
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
Unit
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ ft ]
Total pipe length
[ lbs-oz ]
Pulse
MPa
[ psi ]
Discharge (TH4)
Heat exchanger inlet
(TH3)
Accumulator inlet
Accumulator outlet
°C [ °F ]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
inlet
PUHY-P300YJM-A
-
100/100/100/100/100/100/50
-
kg
A
V
Hz
81
332/332/332/332/332/332/373
2100
2.59/ 0.57
[376/ 83]
82 [180]
0 [32]
-2 [28]
-2 [28]
-2 [28]
22 [72]
- 145 -
Outdoor unit model
PUHY-P650YSJM-A
PUHY-P350YJM-A
20°C/- [68°F/- ]
7°C/ 6°C
[45°F/ 43°F]
7
7
5 [17]
10 [33]
75 [247]
Hi
30.6 [67]
32.8
400
101
0
2100
2.59/ 0.57
[376/ 83]
82 [180]
0 [32]
-2 [28]
-2 [28]
-2 [28]
22 [72]
35 [95]
80 [176]
GB