[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10040
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
Unit
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ ft ]
Total pipe length
[ lbs-oz ]
Pulse
MPa
[ psi ]
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
SCC outlet (TH6)
°C [ °F ]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
outlet
PUHY-P250YJM-A
-
-
kg
A
V
Hz
65
325/325/325/325/325/362
159
2100
3.10/ 0.78
[450/ 113]
91 [196]
47 [117]
7 [45]
7 [45]
27 [81]
19 [66]
42 [108]
- 129 -
Outdoor unit model
PUHY-P550YSJM-A
PUHY-P300YJM-A
27°C/ 19°C
[81°F/ 66°F]
35°C/- [95°F/- ]
6
6
100/100/100/100/100/50
5 [17]
10 [33]
65 [214]
Hi
25.5 [56]
27.5
400
237
2100
3.10/ 0.74
[450/ 107]
89 [192]
47 [117]
7 [45]
7 [45]
27 [81]
19 [66]
42 [108]
27 [81]
6 [43]
71