[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10040
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
Unit
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ ft ]
Total pipe length
[ lbs-oz ]
Pulse
MPa
[ psi ]
Discharge (TH4)
Heat exchanger inlet
(TH3)
Accumulator inlet
Accumulator outlet
°C [ °F ]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
inlet
PUHY-EP200YJM-A
-
-
kg
A
V
Hz
53
2100
2.81/ 0.68
[408/ 99]
82 [180]
2 [36]
0 [32]
0 [32]
0 [32]
42 [108]
- 179 -
Outdoor unit model
PUHY-EP500YSJM-A
PUHY-EP300YJM-A
20°C/- [68°F/- ]
7°C/ 6°C
[45°F/ 43°F]
5
5
100/100/100/100/100
5 [17]
10 [33]
55 [181]
Hi
28.3 [62]
22.9
400
81
332/332/332/332/332
0
2100
2.78/ 0.62
[403/ 90]
82 [180]
2 [36]
0 [32]
0 [32]
0 [32]
43 [109]
37 [99]
80 [176]
GB