Mitsubishi Electric PUHY-P200 Service Handbook page 131

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10040
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ ft ]
Total pipe length
[ lbs-oz ]
Pulse
MPa
[ psi ]
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
SCC outlet (TH6)
°C [ °F ]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
outlet
PUHY-P300YJM-A
27°C/ 19°C
[81°F/ 66°F]
35°C/- [95°F/- ]
3
Unit
3
-
100/100/100
5 [17]
10 [33]
35 [115]
-
Hi
kg
14.0 [31]
A
14.4
V
400
Hz
74
325/325/325
100
-
2.95/ 0.84
[428/ 122]
84 [183]
44 [111]
7 [45]
7 [45]
22 [72]
19 [66]
42 [108]
22 [72]
6 [43]
- 122 -
Outdoor unit model
PUHY-P350YJM-A
27°C/ 19°C
[81°F/ 66°F]
35°C/- [95°F/- ]
4
4
100/100/100/50
5 [17]
10 [33]
45 [148]
Hi
17.6 [39]
17.6
400
95
325/325/325/362
100
-
2.86/ 0.76
[415/ 110]
90 [194]
43 [109]
7 [45]
7 [45]
22 [72]
19 [66]
42 [108]
22 [72]
6 [43]
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents