Chapter 3: Configuration and commissioning

Functional tests

Create a short and open circuit in the zone to test fault reporting for each.
Activate a manual call point to test manual alarm reporting. The control panel should
override any configured delays and activate alarm notification devices and fire
routing (where applicable) immediately.
Activate a detector to test automatic alarm reporting. The control panel should
initiate any configured delays and activate alarm notification devices and fire routing
(where applicable) once the delay time has elapsed.
Using a multimeter, verify that the fault relay is activated when a fault is reported and
that the alarm relay is activated when an alarm is reported.

Response times

Response times for standard events are as follows.
Event
Alarm
Zone fault
Sounder fault
Fire routing fault
Earth fault
attery charger fault
Battery lost fault
Mains fault
Low battery fault
Fuse/protection fault
System fault
Battery high resistance fault
44
Response time
Less than 3 seconds
Less than 30 seconds
Less than 30 seconds
Less than 30 seconds
Less than 100 seconds
Less than 100 seconds
Less than 3 minutes
Less than 3 minutes
Less than 100 seconds
Less than 3 minutes
Less than 100 seconds
Less than 4 hours
Kilsen KFP-CF Series Installation Manual