Appendix A: Configuration presets

NBN S21-100

Configuration presets for NBN S21-100 are as follows.
Four- and eight-zone control panels
Code
Zone EOL
21
Passive
22
Passive, CleanMe
enabled
Note: Alarm relay follows evacuation sounders. CleanMe is not currently available for Kilsen detectors.
Additional configuration characteristics are shown below.
Default sounder delay
Default zone delay
Start/Restart sounders
Inputs and outputs are as follows.
INPUT1
INPUT2
OUT1
OUT2
OUT3
OUT4
64
Warning sounder
Evacuation sounder
outputs
outputs
2
2
2
2
1 minute
0n
Start sounders or restart stopped sounders at access level 2 with or
without a fire alarm event
Remote reset
Delays off
Evacuation sounders
Evacuation sounders
Warning sounders
Warning sounders
Zone type
Automatic
Automatic
Kilsen KFP-CF Series Installation Manual