Chapter 2: Installation
Connecting fire routing equipment
Connect fire routing equipment as shown in the table below.
Operating mode
EN 54-2
EN 54-2 Scandinavia
NEN 2535
The fire routing outputs are supervised for short circuit and open circuit.
Note:
Fire routing in EN 54-2 operating modes makes no distinction between
automatic and manual alarms.

Connecting the mains power supply

WARNING:
Connect the mains power supply before connecting the batteries.
The control panel can be operated at 110 VAC / 60 Hz or 240 VAC / 50 Hz
(+10%/−15%).
Mains power should be sourced directly from a separate circuit breaker in the
building electrical supply distribution board. This circuit should be clearly marked,
have a bipolar disconnect device, and only be used for fire detection equipment.
Feed all mains cables through the appropriate cable knockouts and connect them to
the fuse terminal block as shown in Figure 5 below.
Keep mains cables separate from other cabling to avoid potential short circuits and
interference. Always secure mains cables to the cabinet to prevent movement.
Figure 5: Connecting the mains power supply
For fuse specifications, see Chapter 5 "Technical specifications" on page 49.
12
Fire routing (automatic)
OUT4
OUT3
1. Mains fuse
2. Live
3. Earth
4. Neutral
Fire routing (manual)
OUT4
OUT4
Kilsen KFP-CF Series Installation Manual