Chapter 3: Configuration and commissioning
Display
Menu
Zone type
Access level 2 password
Access level 3 basic password
Access level 3 advanced
password
Control panel PCB serial number
Auxiliary 24 V reset
Sounder operation during a zone test
Use this menu to configure the sounder operation during a zone test. The default
setting for all operating modes is ON.
To configure the sounder
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes quickly to indicate that the sounder
operation during a zone test configuration menu is active.
7. Select a value using the value selection buttons (2 and 4).
8. Press Enter.
9. Save your changes.
The available settings for this feature are shown below.
Display
Description
The internal buzzer and sounders sound for three seconds
when an alarm is activated in a zone test.
The internal buzzer and sounders do not sound when an
alarm is activated in a zone test.
32
Values
Mixed
Automatic
Manual
0 to 4444
0 to 4444
0 to 4444
Read only
ON/OFF
operation during a zone
Operating mode
All
All
All
All
All
All
test:
Kilsen KFP-CF Series Installation Manual