Expansion module output delay
Use this menu to configure an expansion module output delay of up to 10 minutes,
where the feature is available.
To configure an expansion module output delay:
1. For output 1 on expansion module A, set the display as shown below, and then
press Enter.
The Expansion I/O Fault/Disabled LED on the control panel interface and the
Activated LED on the expansion module flashes quickly to indicate that the
module delay menu is active.
2. Select a value from 00 to 10 using the value selection buttons (2 and 4).
3. Press Enter.
4. Repeat steps 1 to 3 as required for each output (1 to 4) on each installed module
(A, B, C, and D) where a delay is required.
5. Save your changes.
Kilsen KFP-CF Series Installation Manual
Chapter 3: Configuration and commissioning
41