Commissioning; Before Commissioning The Control Panel; Commissioning The Control Panel - GE Kilsen KFP-CF2 Installation Manual

Kfp-cf series 2/4/8 -zone conventional fire alarm control panel
Table of Contents

Advertisement

Chapter 3: Configuration and commissioning

Commissioning

Before commissioning the control panel

Before commissioning the control panel, check the following:
• That the control panel has been correctly installed
• That the mains power is 110 VAC or 240 VAC, is connected correctly, and complies
with all requirements described in "Connecting the mains power supply" on page
12
• That there are no short or open circuits in any of the zone circuits
• That all zones have the correct end-of-line termination, as described in
"Terminating zones" on page 9
• That all manual call points have the correct resistance for alarm identification, as
described in "Connecting manual call points" on page 10
• That polarity is observed for all sounder circuits and that all end-of-line resistors
are installed, as described in "Connecting the sounders" on page 11
• That any optional equipment installed (fire routing, alarm, and fault relays, etc.) is
correctly connected
• That the batteries are connected correctly, and comply with all requirements
described in "Connecting the batteries" on page 14
• That all fire alarm system configuration complies with the corresponding
operating mode and local regulations.

Commissioning the control panel

Once all installation, connection, and configuration requirements have been checked
as described above, the control panel can be powered up.
Normal start-up
After starting up the control panel, normal status (standby) is indicated as follows:
• The Supply LED is steady
• The Sounder Delay LED is steady (if a delay has been configured and enabled)
• The Fire Routing Delay LED is steady (if a delay has been configured and enabled)
If any other indicators are on, check your installation thoroughly before proceeding.