Chapter 3: Configuration and commissioning

Common configuration tasks

To enter configuration mode:
1. Remove the control panel cover so that the seven-segment display is visible.
2. Enter a valid access level 3 password (3333 for basic configuration or 4444 for
advanced configuration).
3. Press Enter.
When first entering configuration mode, the Mode LED on the seven-segment display
is steady. For other indications see "Access levels and passwords" on page 18.
To select a menu:
1. Select the required menu using the menu selection buttons (1 and 3).
2. Press Enter.
When a configuration menu has been selected, the Value LED on the seven-segment
display is steady.
To select a value:
1. Select the required value using the value selection buttons (2 and 4).
2. Press Enter.
To exit configuration mode and save your changes:
1. Press Panel Silence.
2. Press Enter.
— or —
1. Set the display as shown below, and then press Enter.
The Panel Silence LED flashes to confirm that a configuration change has been
applied.
Note:
Make all required configuration changes before exiting configuration mode and
saving your changes.
22
Kilsen KFP-CF Series Installation Manual