Auxiliary 24 V Reset; Configuration, Software, And Pcb Identification - GE Kilsen KFP-CF2 Installation Manual

Kfp-cf series 2/4/8 -zone conventional fire alarm control panel
Table of Contents

Advertisement

Chapter 3: Configuration and commissioning

Auxiliary 24 V reset

Use this menu to configure the auxiliary 24 V reset setting, on or off. The default
setting is OFF.
To configure the zone delay:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Resetting the control panel resets the AUX 24V output.
Resetting the control panel does not reset the AUX 24V
output.

Configuration, software, and PCB identification

Use the corresponding menu option (shown below) to see the control panel
configuration version and time stamp, software version, and PCB serial number.
These details may be required for troubleshooting and technical support.
Software version
Configuration version
Configuration time stamp
Configuration date stamp
Control panel PCB serial number
38
Kilsen KFP-CF Series Installation Manual