Expansion module configuration

Add an expansion module

Use this menu, available from the basic or advanced configuration menus, to
configure the number of installed expansion modules. The default value is 00.
To add an expansion module:
1. Set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED flashes quickly to indicate that the module
configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The maximum number of expansion modules that can be installed is shown below.
Two- and four-zone control panels
Eight-zone control panel

Expansion module configuration

Expansion module labels
For configuration purposes expansion modules are labeled A and B (for two- and
four-zone control panels) or A, B, C, and D (for eight-zone control panels).
The label for a given module is defined by its position (left to right) in the control panel
cabinet,. The first expansion module installed is module A, the second B, etc.
See your expansion module installation sheet for installation instructions.
Kilsen KFP-CF Series Installation Manual
Chapter 3: Configuration and commissioning
Up to two expansion modules
Up to four expansion modules
39