GE Kilsen KFP-CF2 Installation Manual page 23

Kfp-cf series 2/4/8 -zone conventional fire alarm control panel
Table of Contents

Advertisement

Access level passwords and indications
The default access level passwords and the corresponding LED and seven-segment
display indications are shown in the table below. The seven-segment display is only
visible when the control panel cover is removed. See Figure 1 on page 4 and Figure 2
on page 5.
Table 5: Access level passwords and indications
Access level
Password
1
None
2
2222
3 basic
3333
3 advanced
4444
Note:
The seven-segment display will default to the custom display (operating mode
menu) when entering basic or advanced configuration if custom zone delay, zone
configuration, or zone type settings have been applied via the advanced
configuration menu.
Kilsen KFP-CF Series Installation Manual
LED
Default display
None
None
The Reset LED is
None
steady
The Reset LED is
flashing
The Reset LED is
flashing
Chapter 3: Configuration and commissioning
Custom display
None
None
19