Main operating controls

See Figure 7. Five controls are used to operate the system as follows:

Figure 7: Main operating controls

Reset
Button
Accept
ACCEPT
RESET
MUTE
BUZZER
Mute
Buzzer
POWER ON
NIGHT
SYSTEM
DAY
ZONE
MORE TIME
POINT
SOUNDERS
REMOTE ALARM
CONTROL OUTPUTS
Optional
Day/Night
Module

Accept button

Press the Accept button after receipt of an alarm. This causes the illuminated indicators to go
steady, and silences the panel buzzer.

Reset button

Press the Reset button to clear all alarms from the system and restore the panel to a normal "no-
alarm" condition.
All displayed alarms are removed, and all illuminated indicators are switched off. Sounders
(unless programmed dynamic) are switched off, and the remote manned centre alarm is restored
to a "no-alarm" condition. If any sensors, call points, or other devices still sense fire, smoke or a
fault, then the panel returns to an alarm condition.

Silence alarms button

Press the Silence Alarms button to silence (switch-off) the sounders.
An alarm condition activates certain sounders throughout the building. Which sounders are
activated depends on the configuration of your system. After pressing the Silence Alarms button,
the Sounders Silenced indicator above the button illuminates.

Sound alarms button

Press the Sound Alarms button to activate all the sounders in the building.
This can be done, for example, to sound a general alert or to restore sounders that were silenced.

Restore disabled alarms button

In Software version 3.10 and earlier: Press the Restore Disabled Alarms button to restore
disabled sounders.
In Software version 3.11 onwards: Press the Restore Disabled Alarms Button to toggle between
Disable All Sounders and Enable All Sounders, as indicated by the Sounders Disabled LED.
Maintenance Staff can disable alarm sounders for routine maintenance. If a fire alarm occurred
while these devices were disabled, the sounders wouldn't work. Pressing the Restore Disabled
Alarms button to enter the Enable All Sounders state also cancels (overrides) any programmed
delays and creates an immediate alarm. Pressing this button doesn't create an alarm, but simply
restores alarm devices to allow them to operate correctly during an alarm.
Revision 11 (05/01/2010)
SILENCE
SOUND
FIRE
FAULT
DISABLED
OTHER
ALARMS
ALARMS
ACTIVE
FAULT
DISABLED DELAYED
PRE-ALM
TEST
ENABLE
CONTROL
RESTORE
DISABLED
ALARMS
ON
OFF
Silence Alarms
Button
Sound Alarms
Button
Restore Disabled
Alarms Button