Operating Instructions - Liebert 130 kVA User Manual

130kva single phase 110v, single & 1 + n system
Table of Contents

Advertisement

User Manual
Hipulse - Single Phase '1+N' UPS System
CHAPTER 5

Operating Instructions

5.1
Introduction
The UPS can be considered to be in one of three operating conditions:
Normal operation
All relevant power switches and circuit breakers closed, the load is powered by the
UPS.
Shutdown
All power switches and circuit breakers open - no load power.
On Static Bypass
The load power is supplied through the mains static bypass line.
considered as an intermediate operating condition being utilized for the purpose of
load transfers between inverter and maintenance bypass or supply under abnormal
operating conditions.
ECOMODE
All the relevant power supply switches and the battery switch are off, and the load is
fed by the Bypass Mains through the UPS Static Transfer Switch, while the Inverter
remains on stand-by.
This chapter contains instructions which enable you to switch between the three
above conditions, to carry out a RESET after a fault transfer and how to switch OFF the
inverter.
5.1.1
General notes
Note1: All the user controls and indicators mentioned in these procedures are identified in chapter 1.
Some of diagrams are repeated here to assist in understanding the procedures.
Note2: The audible alarm may annunciate at various points in these procedures. It can be cancelled
at any time by pressing the 'Alarm Reset' push-button.
Note3: The Hipulse UPS System incorporates an optional automatic boost charge facility which can
be used in systems containing conventional flooded lead-acid batteries. If this type of battery
is used in your installation you may notice that the battery charger voltage may be greater
than its nominal (432V d.c. for 380V a.c., 446V d.c. for 400V a.c. and 459V d.c. for 415V a.c.
system) when the mains supply returns from a prolonged outage. This is the normal response
of the boost charge facility; the charger voltage should return to normal after a few hours.
5.1.2
Power Switches
The UPS can be separated by means of power switches, mounted inside the cabinet
and accessible after opening the front door, which has a key.
The location of the UPS power switches is shown in Figure 5-1. The UPS module
power switches are:
Q1 - Input MCCB: connects the UPS with he mains supply.
o
Q2 - Bypass Isolator: connects the UPS with the bypass supply.
o
Q3 - Maintenance Bypass Isolator (Padlocked) permits supply of the load
o
directly by the bypass line for maintenance of the UPS module.
The internal maintenance bypass must not be used when the UPS system is comprised of more
than two UPS modules in parallel.
Q4 - Output Isolator: connects the output of the UPS to the load.
o
Note: The battery interrupter is not expected inside of the UPS and should be installed in the proximity
of the respective battery bank.
31
130 kVA - 110V
This may be

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hipulse

Table of Contents