Liebert 130 kVA User Manual page 41

130kva single phase 110v, single & 1 + n system
Table of Contents

Advertisement

User Manual
Hipulse - Single Phase '1+N' UPS System
3.2.3
Emergency Stop
If an external Emergency Stop facility is required it is connected to terminals 5 & 6 of
the Auxiliary Terminal Block (X4) and connect the 'normally closed' remote stop switch
between these two terminals using shielded cable.
terminals 5 & 6 must be linked-out as shown in Figure 3-3.
Note:
The Emergency Stop action within the UPS shuts down the rectifier, inverter and static bypass
and trips the battery circuit breaker. It does not however internally disconnect the input mains supply.
If required, this additional action can be facilitated by feeding the UPS input via a circuit breaker
which can be tripped by a second contact of the Emergency Stop switch.
Note:
Terminals 11 and 12 of the Auxiliary Terminal Block (X4) are connected to a normally closed
contact of the UPS Display Panel Emergency Stop button and go open circuit when the button is
pressed. This output can be used as part of a wider Emergency Stop system to initiate an external
action (such as tripping an external supply breaker)
3.2.4
Back Feed Protection
Using an auxiliary terminal (pins 9-10 of connector X4) the UPS provides a normally
open contact to be used for opening of an external circuit protection device, to protect
the operator against back feed of energy resulting from a short-circuit fault of the
Bypass line SCRs. This auxiliary contact can be used, for example, in series with an
external low voltage source, in order to supply the trip coil of an automatic circuit
breaking device, located upstream of the UPS Bypass mains input.
energy being backfeed the auxiliary circuit will activate closing the normally open
contact and as a result opening of the external circuit-breaking device; the UPS is
disconnected from the Bypass mains supply.
auxiliary contact are 50V (a.c. or d.c.) @ 1 Amp.
To Battery
+
Sensor
Temperature
(Optional)
+
BATTERY
CIRCUIT
BREAKER
UPS CABINET
+
Fig 3-3: Battery Connection
21
3
2
1
X3
X4
X5
X6
X7
V<
X8
X9
X2
X10
1 2 3 4 5
X1
X3
Battery C.B.
1
2
Controller
3
4
5
6
7
8
9
10
11
12
If this facility is not used then
The electrical characteristics of the
130 kVA - 110V
In the vent of

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hipulse

Table of Contents