Hipulse - Single Phase '1+N' UPS System
7.
OVERLOAD SHUTDOWN
8.
OUTPUT SWITCH OPEN
9.
BYPASS SWITCH OPEN
10.
BATTERY C.B. OPEN
11.
BATTERY: FUSE FAIL
12.
BATTERY: TEST FAILED
13.
DC BUS: UNDERVOLTAGE
overload present.
This message informs the operator that the load has been
transferred to bypass due to an inverter overload.
This is a status alarm.
The output switch must be selected
'CLOSED' at all times except when operating on the Maintenance
bypass supply.
This is a status alarm. The bypass input switch must be closed all
the times.
This is a status indication only. Note that if the UPS is operating
with the Battery circuit breaker open, and the mains power fails,
then the UPS output will also fail together with load power, since
the inverter has no battery backup.
This problem should be rectified as soon as possible. If the mains
power fails then the UPS output will also fail together with load
power, since there is no battery backup.
The system has carried out a test of the battery. If this alarm is not
accompanied by a [BATTERY C.B. OPEN] or [BATTERY: FUSE FAIL]
message then a full check of the Battery bank is required.
When the inverter is operating on the battery this message is
displayed on the condition when battery voltage has fallen below a
preset value. If the input a.c. power cannot be restored, you should
shut down your loads.
58