Hipulse - Single Phase '1+N' UPS System
5.9
Procedure to completely switch ON/ OFF the UPS at the
UPS Display Control Panel:
MEASUREMENT
MEASUREMENT
>FUNCTION
>FUNCTION
MAINTENANCE
MAINTENANCE
SETUP
SETUP
WRITE
WRITE
MOVE
MOVE
EXIT ESC
EXIT ESC
ENTER PASSWORD
ENTER PASSWORD
00000000
00000000
BATTERY TEST
BATTERY TEST
GENERATOR
GENERATOR
PANEL SETUP
PANEL SETUP
>NEXT PAGE
>NEXT PAGE
MODEM CONNECTION
MODEM CONNECTION
>ON/OFF UPS CONTROL <
>ON/OFF UPS CONTROL <
RELOAD UPS DATA
RELOAD UPS DATA
RESET BUFFERS
RESET BUFFERS
>INVERTER OFF
>INVERTER OFF
BYPASS
BYPASS
RECTIFIER
RECTIFIER
RECTIFIER
RECTIFIER
ROTATE
ROTATE
START
START
EXIT
EXIT
INVERTER
INVERTER
1. From the Default window, press the ENTER key:
the Main Menu window will display:
<
<
2. Select FUNCTION and press ENTER key:
Before being allowed into the FUNCTION windows
SAVE
SAVE
you are requested to enter a password.
achieved by pressing the UP arrow key repeatedly
until the first digit displays the character required,
you then press the DOWN arrow key once to move
on to the second digit. This action is repeated for
all eight digits. When the PASSWORD has been
completed press the ENTER key.
CAUTION
This operation gives the operator access to modify
UPS's operating mode, it is advised that only trained
qualified personnel should attempt to do that.
3. You have now access to all function windows.
Press the DOWN arrow key until the cursors have
selected NEXT PAGE – press the enter key.
<
<
4. Press the DOWN arrow key until the cursors
have selected ON/OFF UPS CONTROL.
Press the enter key.
CAUTION
The following window allows the operator to select
the UPS inverter ON or OFF, select the rectifier ON or
OFF, select the rectifier to manual or float voltage and
a switch OFF the line (bypass) voltage to the load.
<
<
ON
ON
IF YOU ARE NOT SURE WHAT YOU ARE DOING,
ON
ON
MAN
MAN
NORMAL OPERATION:
ESC
ESC
5a. Ensure INVERTER is selected by the cursors
ON
ON
and press the ENTER key.