Liebert 130 kVA User Manual page 34

130kva single phase 110v, single & 1 + n system
Table of Contents

Advertisement

User Manual
Hipulse - Single Phase '1+N' UPS System
3.1.2
Cable rating
UPS
3 Phase Input Mains with full
battery re-charge
Rating
(kVA)
(less 5% for 12 pulse)
380V
400V
30
63
60
40
84
50
105
100
60
126
119
80
165
157
120
245
233
130
259
247
150
300
285
3.1.3
General Notes
The following are guidelines only and superseded by local regulations and codes of
practice where applicable:
1. The neutral conductor should be sized same as the output/ bypass current.
2. The earth conductor should be sized for carrying fault current for atleast 3 to 5
seconds or as guided by local electrical rules.
3. Consideration should be given to the use of paralleled smaller cables for heavy
currents, as this can ease installation considerably.
4. When sizing battery cables, a maximum volt drop of 3V d.c. is permissible at the
current ratings given in Table 3-1.
3.1.4
Cable Connections
The rectifier input, bypass, output and battery power cables (all require lug type
terminations) and are connected to busbars situated below the power isolator
switches - as shown in figure 3.1 for 80kVA and fig 3.2 for 120 /160/ 200kVA.
A terminal block X3 is used for connecting the control cables to the battery circuit
breaker and a second terminal block X4 is used for the external emergency stop
facility, external OFF inverter, ext. Bypass, etc. these are female spade type
connections (Fast-on 6.3 x 0.8) and are described later in Section 3.2
3.1.5
Safety earth
The safety earth busbar is located between the Bypass and Output power supply
connections as shown in the figure 3.1. The safety earth cable must be connected to
the earth busbar and bonded to each cabinet in the system.
All cabinets and cable trunking should be earthed in accordance with local
regulations.
NOMINAL CURRENT (Amps)
1 Phase Output at full load
415V
110V
115V
58
272
260
80
77
364
349
96
454
434
115
545
521
151
727
695
223
1090
1043
238
1181
1130
275
1363
1304
Table 3-1 UPS Module cabinet power cable rating
14
Battery at minimum
Battery Voltage
120V
380V
400V
250
83
80
334
110
106
416
137
133
500
164
159
666
219
213
1000
329
319
1083
357
346
1250
412
399
130 kVA - 110V
415V
77.5
103
129
155
206
310
336
387