BYP: XFER COUNT BLOCK
31.
BATTERY: GROUND FALUT
32.
BACKFEED FAULT
In addition to the above message there are a number of software alarms (i.e. BAD
EEPROM, BACK-UP, BATTERY LOW etc.) that will require attention from a qualified
service engineer.
This message informs the operator that the load has been
transferred to the bypass more than eight times in one minute.
After eight transfers the load will remain on bypass. This message
could be initiated by a load causing the UPS to overload, it requires
investigation.
This message informs the operator that the battery is not longer
isolated from ground and there is danger of electrocution.
This message informs the operator that the failure of the bypass
static devices has resulted in voltage being fed back to the bypass
supply input.