Liebert 130 kVA User Manual page 81

130kva single phase 110v, single & 1 + n system
Table of Contents

Advertisement

User Manual
Hipulse - Single Phase '1+N' UPS System
30.
BYP: XFER COUNT BLOCK
31.
BATTERY: GROUND FALUT
32.
BACKFEED FAULT
In addition to the above message there are a number of software alarms (i.e. BAD
EEPROM, BACK-UP, BATTERY LOW etc.) that will require attention from a qualified
service engineer.
This message informs the operator that the load has been
transferred to the bypass more than eight times in one minute.
After eight transfers the load will remain on bypass. This message
could be initiated by a load causing the UPS to overload, it requires
investigation.
This message informs the operator that the battery is not longer
isolated from ground and there is danger of electrocution.
This message informs the operator that the failure of the bypass
static devices has resulted in voltage being fed back to the bypass
supply input.
61
130 kVA - 110V

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hipulse

Table of Contents