1.4 Product specification and performance
General specification
Model
Power Rating
Frequency (Hz)
Input
Power Factor
Battery
Voltage regulation
Output
Power Factor
Frequency tolerance
Overload capacity
Current crest ratio
Operating environment
Temperature
0 -40
¡æ ¡æ
Note: If the UPS is installed or uesd in a place where the altitude is above than 1000m, the
output power must be derated in use, please refer to the following:
Altitude (M)
Derating power
C6K(e)
6kVA/4.2kW
50
Voltage
(176-276)VAC
Current
31A max.
Frequency
46Hz~54Hz
>0.98(Full load)
Voltage
240VDC
Current
24A max.
Voltege
220VAC
Current
27A
Distortion
105%-130% load transfers to bypass mode after 10 minutes
>130% load transfers to bypass mode after 1 second and shutdown
Humidity
<95%
1000
1500
2000
100%
91%
95%
1. Brief introduction
C6KS(e)
6kVA/4.2kW
50
(176-276)VAC
31A max.
46Hz~54Hz
>0.98(Full load)
240VDC
24A max.
220VAC
27A
¡À
1%
0.7 lag
Synchronized 46-54Hz in Line mode(AC mode)
¡À
0.1% of normal frequency in Battery mode
THD<2% Full load (Linear load)
the output after 1 minute
3:1 maximum
Altitude
<1000m
2500
3000
3500
86%
78%
82%
C10K(e)
C10KS(e)
10kVA/7kW
10kVA/7kW
50
50
(176-276)VAC
(176-276)VAC
50A max.
50A max.
46Hz~54Hz
46Hz~54Hz
>0.98(Full load)
>0.98(Full load)
240VDC
240VDC
40A max.
40A max.
220VAC
220VAC
45A
45A
Storage temperature
0 -40
¡æ ¡æ
4000
4500
5000
74%
67%
70%
3