C h a p te r 3 I n s t all at ion i ns tr uction s

3.1 Installation Notice

1) The installation of Castle EX series products must be performed in compliance with the
electrical code by professional personnel.
2) Install the UPS in a clean and stable environment that is free of vibration, dust, high
humidity, Àammable gas, and Àammable liquid or caustic substance.
3) To ensure normal UPS performance, ambient temperature should range between 0-40
If temperature exceeds 40
of the rated amount along with every increase of temperature by 5
bient temperature for normal UPS performance should not exceed 50
4) It is suggested that battery pack should work within a temperature range from15
25
.
5) Altitude for normal UPS function should not exceed 1000m. Should UPS be intended
for application above 1000m, progressive decrease of rated output should be applied as
listed in the following chart:
Altitude(m)
1000
Derating
100
coef¿cient

3.2 Installation space

3C3 EX 20KS/30KS/40KS series utilizes forced fan cooling and installation spot should
make allowance for ventilation. Meanwhile, inside maintenance should be carried out
from the front side and therefore maintenance space should also be considered in advance.
Refer to the following ¿gure for installation space:
, maximum load should be decreased progressively by 12%
1500
2000
2500
95
91
86
3000
3500
82
78
8
. The maximum am-
.
4000
4500
5000
74
70
67
.
to