UPS
Performances
Technology High-Frequency Line-Interactive
•
Automatic voltage regulation Booster/Fader
•
Output voltage waveform Sinewave
•
Input voltage tolerances 160V/294V, adjustable to 150V/294V via supplied UPS-Driver
•
software
Frequency 50/60 Hz, auto-select
•
Output voltage on battery power 230V (adjustable to 200/220/240V via supplied UPS-
•
Driver software)
Features
Automatic battery test Weekly (interval adjustable via supplied UPS-Driver software)
•
Hot swappable batteries
•
Cold start
•
Deep discharge protection
•
UPS-Driver for Windows® Settings: Input voltage tolerances,
•
Sensitivity, Battery test, ON/OFF conditions
•
Standards
Safety EN 50091-1-1/EN60950(RD),IEC 60950,Tüv
•
GS-Mark, IEC 60 945
•
Electromagnetic compatibility EN 50091-2,EN 50022/B,IEC 62040-2,IEC
•
61000-3-2,IEC 61000-3-3, IEC 60 945
•
Design, production and services ISO 9001
•
Marking CE, TÜV GS-Mark, DnV
•
Dimensions and weight
•
Tower dimensions (HxWxD in mm) 150x237x415
•
Tower weights (in kg) 10.5
•
S
PECIFICATIONS OF THE
Power (VA / Watts) at full load 1500 VA / 1050 W
•
# of receptacles 6 w/ 2 switchable
•
Part Number UPS + EMC filter 66 353 + 5102174900
•
Part number extra battery module 66 356
•
Part number alarm card (dry contacts) 66 246
•
Features Benefits
True On Line Technology (1) Utility power is constantly conditioned within very tight
•
limits without draining the batteries
Smart battery management The built-in microprocessor optimizes the charging sequence
•
to prolong battery lifetime
Complete front panel display Check the battery or capacity levels for peace of mind. Get
•
valuable information on the UPS status and operating parameters.
44