Plan Wall Finish

Non-combustible cement board
The L1 Linear fi replace requires a 1/2"
(13 mm) thick non-combustible cement board
to be used as a wall surface immediately
surrounding the unit on each side—see
diagram for minimum coverage.
Extending the cement board well beyond the
minimum shown will help avoid cracking due
to differential expansion of materials.
Pre-drill cement board with oversized holes
and do not over-tighten screws to avoid
cracking due to heat expansion.
Standard gypsum wall board may be used
beyond the perimeter of the cement board.
Finishing around trims
Additional non-combustible material such as
tile, etc., may be applied over top of the wall
surface or you may choose to leave it fi nished
clean with no tile, etc. Be aware that a trim
is always required and that only the wider
1550 style trim will accept tile, etc. tucked
behind it (up to 1 inch thick). Additional non-
combustible fi nishes may be butted up to the
narrow 1555 trim or the 1570RCS but should
not cover these trims.
1 /
( 2
4 "
3 5
m
m
P o
)
( i n
Wider trim (1550)
can adjust up to 1" off
surface of cement board
Installation
(1130 mm)
Minimum cement board dimensions
s s i
b l e
t h
s c r
e d
e w
e s
i g n
l o c
a t e
d
Narrow trim (1555)
mounts directly over
the cement board
Gypsum board
up to perimeter
of cement board
Min.
20-1/2"
(521 mm)
Min.
44-1/2"
14-3/4"
(375 mm)
Min.
9-1/4"
(235 mm)
Board flush with
bottom of heater;
add extra if
overlapping
framing.
a r d
o f
f l u
h e
s h
o v
a t e
e r l
w i
r ; a
a p
t h
d d
p i n
b o
e x
g f
t r a
r a m
i n g
QUALIFIED
INSTALLER
Min. 48"
(1219 mm)
40"
(1016 mm)
1/2" (13mm) thick
non-combustible
cement board
Wider trim (1570)
mounts directly over
the cement board
37