ADEMCO VISTA-20P Installation And Setup Manual page 31

Hide thumbs Also See for VISTA-20P:
Table of Contents

Advertisement

FIELD
TITLE and DATA ENTRIES
Trouble Report Code
*60
0 = no report
1st digit non-zero = send report
Bypass Report Code
*61
0 = no report
1st digit non-zero = send report
AC Loss Report Code
*62
0 = no report
1st digit non-zero = send report
Low Bat Report Code
*63
0 = no report
1st digit non-zero = send report
Test Report Code
*64
0 = no report
1st digit non-zero = send report
Open Report Code
*65
0 = no report
1st digit non-zero = send report
Arm Away/Stay Report Code
*66
0 = no report
1st digit non-zero = send report
RF Trans. Low Batt. Report Code
*67
0 = no report
1st digit non-zero = send report
Cancel Report Code
*68
0 = no report
1st digit non-zero = send report
Alarm Restore Report Code
*70
0 = no report
non-zero = send report
Trouble Restore Report Code
*71
0 = no report
1st digit non-zero = send report
Bypass Restore Report Code
*72
0 = no report
1st digit non-zero = send report
AC Restore Report Code
*73
0 = no report
1st digit non-zero = send report
Low Bat Restore Report Code
*74
0 = no report
1st digit non-zero = send report
RF Xmtr Low Batt. Restore Code
*75
0 = no report
1st digit non-zero = send report
Test Restore Report Code
*76
0 = no report
1st digit non-zero = send report
EXPLANATION
This will be sent if a zone has a trouble condition.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
This will be sent when a zone is manually bypassed.
UL: Required for UL commercial burglar alarm installations.
Timing of this report is random with up to a 4-hour delay. If AC
restores before the report goes out, there is no "AC RESTORE"
report.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
Sent when a low-battery condition exists in the system's battery.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
Sent periodically to test that the communicator and phone lines are
operational. Frequency of report is set in Scheduling mode (event 11).
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
This is sent upon disarming of the system in the selected partitions.
UL: Required for UL commercial burglar alarm installations.
This option allows for independent programming of Away and Stay
reports for each partition, including the common lobby.
NOTE: "OPEN" reports are not sent if the associated closing report
is not enabled.
Sent when a wireless transmitter low-battery condition exists.
UL installations: must be enabled if wireless devices are used.
This is sent upon disarming of the system after an alarm condition
was reported.
Sent when an alarm zone is restored to its non-faulted condition.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
This is sent when a trouble in a zone is restored
UL: Required for UL commercial burglar alarm installations.
This is sent when a zone that has been bypassed is unbypassed.
UL: Required for UL commercial burglar alarm installations.
Sent when AC power has been restored after an AC power outage.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
Sent when a system low-battery condition is restored to normal.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
Sent when a transmitter's low battery condition is restored (i.e., new
battery installed).
UL installations: must be enabled if wireless devices are used.
Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
This is sent when the Test mode is exited.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
4-5